Offline UPS |
Model |
PC-AC UPS |
Capacity | 5KV |
DC BUS | 72V |
Phisical |
Enclosure Protection | IP-20 |
Cooling | Forced Air |
Cable Entry | Back side bottom |
Diamensions in mm-DHW & weight (Aproximate) | 510×520×200/40kg |
LED Indication | .Mains on .Charger on .Inverter on .Battery Low .Trip |
LCD Indication | .input voltage .output voltage .battery voltage .load current |
Productions |
|
Features | Sinewave UPS with AVR for lightinr load |
Testing Standerd | As per IEC 62040-3) |
"UPS with digital mains voltage conditioning using zero voltage switching extends the life of your load and the uptime of your process by 35% as compared to conventional inverter or static UPS - Considering the investment on such equipment mains voltage conditioning is a basic feature.
Be it your office or home, give your sensitive gadgets, PCs, home theatres and other electronic gadget the extra 35% life.
With Zero transfer time, PC-AC UPS is a perfect substitute for Online UPS and saves approximately 30-40% of electricity charges in comparison.
Input |
Input Voltage | 230V |
Input Voltage Window | 160-270V |
Input Frequency | 50Hz ± 10% |
Output |
Transfer Time |
|
Voltage on Mains | 220V ± 10% |
Voltage on Inverter | 230V Single Ø ± 1% |
Power Factor | 0.8 lag |
Frequency on inverter mode | 50Hz ± 1Hz |
Waveform on inverter mode | Pure sinewave |
Overload capacity | 100% continues-125% -1 Minute |
Transient response | Remain within +/- recover to normal within 20msed |
Nominal output current | 17.4 |
Mode of Operation | Designed for Continuous operation |
Efficiency |
Efficiency - on Inverter Mode | <85% |
Charger Type | CVCC |
Charging Current Standard | 1 -6 A |
Higher charging current | Provided on request |
Acousting Noise level | 60db @ 1.5 meter |
Operating ambient Temperature | 0 to 40°C |
Humidity | Up to 95% RH Non condensing |
Altitude | <3000 Feet above sea level (without derating) |